System Event Log Troubleshooting Guide for Intel
®
S5500/S3420 series Server Boards
Processor subsystem
Revision 1.0 Intel order number G74211-001 43
Table 45: Processor Status Sensors Next Steps
Sensor
Number
Sensor Name
Event Trigger Offset
Description
Next Steps
Hex
Description
60h
P1 Status
01h
Thermal trip
The processor exceeded the
maximum temperature.
This event normally only happens due to failures of the thermal solution:
1. Verify heatsink is properly attached and has thermal grease.
2. If system has a heatsink fan, ensure the fan is spinning.
3. Check all system fans are operating properly
4. Check that the air used to cool the system is within limits (typically 35°C)
07h
State Asserted
Indicates processor is present
61h
P2 Status
01h
Thermal trip
The processor exceeded the
maximum temperature.
07h
State Asserted
Indicates processor is present