Server Component Installations and Upgrades—NSC2U Server
Ventilation — The equipment rack must provide sufficient airflow to the front of the
server to maintain proper cooling. It must also include ventilation sufficient to exhaust
a maximum of 1200 BTU per hour for a fully loaded server system using the IP Network
Server NSC2U.
It is important to note that this measurement is the maximum, and a minimum or
typical system could use much less. You may want to calculate the BTU/hour
measurement more accurately for your configuration. An extra 500 BTU/hour over
many systems would translate into a large error calculating air conditioning capacity.